101
EN
Service class 2
Service class 3
Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time
The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.
108 Islanding detected 1. Islanding detected 1. Automatic correction
2. Severe disturbances in pub-
lic mains
2. Automatic correction
3. Bad contact: wall bracket <-
> filter board
3. Check AC wall bracket
screws
4. Grid Impedance out of per-
mitted values
4. Contact utility
5. Bad AC connection 5. Check AC connection
6. Ripple control signals 6. Report to TSI specialist
7. Measuring error on the filter
board
7. Change filter board
112 RCMU Error 1. Old filter board software
(<4.6)
1. Software update
2. Permanent grounding error 2. Check AC / DC connections
Code Description Behaviour Remedy
Code Description Behaviour Remedy
240 AFCI tripping No error, AFCI tripped. Error
visible for 4 Seconds then 241
Automatic correction
241 - 242 AFCI tripping Arc occurred, to resume opera-
tion press enter twice (first 242
then operation is resumed)
Check PV generator
245 AFCI selftest fail 1. Selftest routine failed due to
detection failure
1. Restart inverter or do a soft-
ware update
2. Change filter board
247 AFCI currentsensor fail 1. Data from primary and sec-
ondary current sensor don‘t
correspond
1. Restart inverter or do a soft-
ware update
2. Change filter board
Code Description Behaviour Remedy
301 Current peak on the mains
supply detected
1. Voltage drop on the public
mains
1. Automatic correction
2. Grid Impedance out of per-
mitted values
2. Contact utility
3. Bad contact: wall bracket <-
> inverter
3. Check AC wall bracket
screws
4. Measuring error on the filter
board
4. Change filter board
5. Wrong power limit on device 5. Change AC board