169
EN
Documentation
Documentation - The electrician who performed the tests is responsible for compiling the proper docu-
mentation
- Document all completed tests in a test record. Enter both the measured values and
the equipment/calibration data used
- If an individual test cannot be performed, the resulting decision must be justified and
documented by the examiner
- Any device that fails a test must be clearly marked as unsafe and the operator in-
formed. The device may no longer be used.
The test record for the "Safety inspection" is available on the Fronius Partnerweb.