Insulation resistance
- The measuring voltage value shown on the measuring device must be at least the
same as the rated voltage to earth of the device to be tested, however it must be no
less than 500 V DC voltage.
- The measuring current must be at least 1 mA (this corresponds to a load resistance
of 0.5 M).
Ground conductor current
- The effective inner resistance of the ground conductor measuring device must not ex-
ceed 5 . In the event of higher resistances, measures must be adopted to prevent
dangerous contact voltages.
- The measuring range must cover at least 0.25 mA to 19 mA.
- The testing equipment must evaluate the measured current as an effective value re-
gardless of the curve form.
Contact current
- The effective inner resistance of the contact current measuring device must be 1 k
to 2 k.
- Should the current measuring circuit be inadvertently connected to a voltage up to
120% of the nominal grid voltage, the user must not be put at risk and the testing circuit
must not be damaged.
- The testing equipment must evaluate the measured current as an effective value re-
gardless of the curve form.

Table of Contents

Other manuals for Fronius Symo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Symo and is the answer not in the manual?

Fronius Symo Specifications

General IconGeneral
THD< 3 %
Number of MPP Trackers2
Protection ClassIP65
Frequency Range50 / 60 Hz
Operating Temperature Range-25°C to +60°C
Power Range3.0 kW - 20.0 kW
AC Output Voltage230 V
CommunicationEthernet
Warranty5 years
ModelSymo

Related product manuals