MHT258a (Engl.)6-19
Function (Input signal) number assigned to
system para.1 to 8 (CONT1 to CONT8)
Function (Output signal) assigned to
system para.31 to 35 (OUT1 to OUT5)
0: Not assigned 37: Position control 0: Not specified 32: Alarm code 0
1: Run command [RUN] 38: Torque control 1: Ready [RDY] 33: Alarm code 1
2: Forward command [FWD] 43: Override valid 2: Positioning end [PSET] 34: Alarm code 2
3: Reverse command [REV] 44: Override1 14: Brake timing 35: Alarm code 3
5: Origin return [ORG] 45: Override2 15: Dynamic braking 36: Alarm code 4
6: Origin LS [LS] 46: Override4 16: Alarm detection [ALM] 38: +OT detection
7: +OT 47: Override8 17: Fixed, passing point 1 39: -OT detection
8: -OT 48: Interrupt input valid 18: Fixed, passing point 2 40: Origin LS detection
10: Forced stop [EMG] 49: Interrupt input 20: OT detection 41: Forced stop detection
11: Alarm reset [RST] 50: Deviation clear 22: Origin return end
14: ACC0 51: X1 23: Deviation zero
16: Position preset 52: X2 24: Speed zero [NZERO]
27: Pulse train ratio 1 53: X3 25: Speed arrive [NARV]
28: Pulse train ratio 2 54: Free-run [BX] 26: Torque limit detection
29: P-action 55: Edit permit command 27: Overload early warning
30: Torque limit 56: Current position output 28: CPU ready [CPURDY]
34: External fault input 29: Edit permit on
31: Address error
Set a number corresponding to signal name at desired system parameter, so that the signal can be assigned to the terminal.
■ Setting example
Set “1” at the “system parameter 1” so that the terminal [CONT1] of the control input/output connector [CN1] functions as the input terminal
for the “Run command” [RUN] signal.
■ Duplicated allocation
For the control input terminals, a signal cannot be assigned to more than one terminal simultaneously.
However, only the following signals can be assigned to more than one terminal:
・Forced stop (10)
・Free-run (54)
・External fault input (34)
In case of “forced stop” and “external fault input”, the motor will stop forcibly if an input terminal is off.
In case of “free-run”, the motor will be in free-run status if an input terminal is turned on.
If the signals other than the above have been assigned to more than one terminal, a control signal error [CtE] will be detected when turning
on power supply again.
For the control output terminals, a signal can be assigned to more than one terminal simultaneously.
Each terminal goes on or off at the same timing.
■ Interrupt input (49)
Be sure to assign the interrupt input (49) to any one of the terminals [CONT1] to [CONT8].
In case it is assigned to [CONT9] through [CONT13], a control signal error [CtE] will be detected.
■ Always valid
The functions can be assigned to the terminals by setting a numerical value at the system para. 1 to 8.
Similarly, the assigned functions can be always valid by setting the function (signal) number at the system para. 87 or 88. (See 6.3.6.)
Remark : If a number has been assigned to system para. 1 to 8 and system para. 87, 88 simultaneously, a control signal error [CtE] will not
be detected.
The assigned signal is always effective.