MHT258a (Engl.)6-26
System parameter
The system parameter is used for the function setting of the control input/output terminals of amplifier.
Changed setting of most parameters is effective only after turning off and on power.
System parameter for RYS-V type (1/2)
No. Name Setting range Initial value Change
01 CONT1 signal assignment 0 to 56 (in 1 steps) 1 Power
02 CONT2 signal assignment 0 to 56 (in 1 steps) 2 Power
03 CONT3 signal assignment 0 to 56 (in 1 steps) 3 Power
04 CONT4 signal assignment 0 to 56 (in 1 steps) 11 Power
05 CONT5 signal assignment 0 to 56 (in 1 steps) 51 Power
06 CONT6 signal assignment 0 to 56 (in 1 steps) 52 Power
07 CONT7 signal assignment 0 to 56 (in 1 steps) 27 Power
08 CONT8 signal assignment 0 to 56 (in 1 steps) 37 Power
09
to
21
Unused 0
22 Parameter RAM storage 1 0: Not assigned 1 to 99: Basic parameter No. 0 Power
23 Parameter RAM storage 2 0: Not assigned 1 to 99: Basic parameter No. 0 Power
24 Parameter RAM storage 3 0: Not assigned 1 to 99: Basic parameter No. 0 Power
25 Parameter RAM storage 4 0: Not assigned 1 to 99: Basic parameter No. 0 Power
26 Parameter RAM storage 5 0: Not assigned 1 to 99: Basic parameter No. 0 Power
27 Parameter RAM storage 6 0: Not assigned 1 to 99: Basic parameter No. 0 Power
28 Parameter RAM storage 7 0: Not assigned 1 to 99: Basic parameter No. 0 Power
29 Parameter RAM storage 8 0: Not assigned 1 to 99: Basic parameter No. 0 Power
30 Parameter RAM storage 9 0: Not assigned 1 to 99: Basic parameter No. 0 Power
31 OUT1 signal assignment 0 to 41 (in 1 steps) 1 Power
32 OUT2 signal assignment 0 to 41 (in 1 steps) 28 Power
33 OUT3 signal assignment 0 to 41 (in 1 steps) 24 Power
34 OUT4 signal assignment 0 to 41 (in 1 steps) 0 Power
35 OUT5 signal assignment 0 to 41 (in 1 steps) 0 Power
Function (Input signal) number assigned to
system para.1 to 8 (CONT1 to CONT8)
Function (Output signal) assigned to
system para.31 to 35 (OUT1 to OUT5)
0: Not assigned 37: Position control 0: Not specified 32: Alarm code 0
1: Run command [RUN] 38: Torque control 1: Ready [RDY] 33: Alarm code 1
2: Forward command [FWD] 43: Override valid 2: Positioning end [PSET] 34: Alarm code 2
3: Reverse command [REV] 44: Override1 14: Brake timing 35: Alarm code 3
5: Origin return [ORG] 45: Override2 15: Dynamic braking 36: Alarm code 4
6: Origin LS [LS] 46: Override4 16: Alarm detection [ALM] 38: +OT detection
7: +OT 47: Override8 17: Fixed, passing point 1 39: -OT detection
8: -OT 48: Interrupt input valid 18: Fixed, passing point 2 40: Origin LS detection
10: Forced stop [EMG] 49: Interrupt input 20: OT detection 41: Forced stop detection
11: Alarm reset [RST] 50: Deviation clear 22: Origin return end
14: ACC0 51: X1 23: Deviation zero
16: Position preset 52: X2 24: Speed zero [NZERO]
27: Pulse train ratio 1 53: X3 25: Speed arrive [NARV]
28: Pulse train ratio 2 54: Free-run [BX] 26: Torque limit detection
29: P-action 55: Edit permit command 27: Overload early warning
30: Torque limit 56: Current position output 28: CPU ready [CPURDY]
34: External fault input 29: Edit permit on
31: Address error