4-48 PQM Power Quality Meter GE Power Management
4.5 S4 ALARMS/CONTROL 4 PROGRAMMING
4
4.5.6 DEMAND ALARMS
Figure 4–30: SETPOINTS PAGE 4 – ALARMS/CONTROL / DEMAND
]] SETPOINTS
]] S4 ALARMS/CONTROL
] DEMAND
]
PHASE A CURRENT DMD
RELAY: OFF
PHASE A CURRENT DMD
LEVEL
≥
≥≥
≥
100 A
PHASE B CURRENT DMD
RELAY: OFF
]] SETPOINTS
]] S5 TESTING
SETPOINT
Range: ALARM, AUX1, AUX2, AUX3, OFF
PHASE A CURRENT DMD
LEVEL
≥
≥≥
≥
100 A
PHASE C CURRENT DMD
RELAY: OFF
PHASE C CURRENT DMD
LEVEL
≥
≥≥
≥
100 A
NEUTRAL CURRENT DMD
RELAY: OFF
NEUTRAL CURRENT DMD
LEVEL
≥
≥≥
≥
100 A
Range: 10 to 7500, Step: 1 A
3
Φ
ΦΦ
Φ
POS REAL PWR DMD
RELAY: OFF
3
Φ
ΦΦ
Φ
POS REAL PWR DMD
LEVEL
≥
≥≥
≥
1000 kW
3Φ
ΦΦ
Φ POS REACT PWR DMD
RELAY: OFF
Range: ALARM, AUX1, AUX2,
AUX3, OFF
3
Φ
ΦΦ
Φ
POS REACT PWR DMD
LEVEL
≥
≥≥
≥
1000 kvar
3
Φ
ΦΦ
Φ
NEG REAL PWR DMD
RELAY: OFF
3
Φ
ΦΦ
Φ
NEG REAL PWR DMD
LEVEL
≥
≥≥
≥
1000 kW
3
Φ
ΦΦ
Φ
NEG REACT PWR DMD
RELAY: OFF
3
Φ
ΦΦ
Φ
NEG REACT PWR DMD
LEVEL
≥
≥≥
≥
1000 kvar
Range: 1 to 65000; Step: 1 kW
3
Φ
ΦΦ
Φ
APPARENT PWR DMD
RELAY: OFF
3
Φ
ΦΦ
Φ
APPARENT PWR DMD
LEVEL
≥
≥≥
≥
1000 kVA
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 10 to 7500, Step: 1 A
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 10 to 7500, Step: 1 A
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 10 to 7500, Step: 1 A
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 1 to 65000; Step: 1 kvar
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 1 to 65000; Step: 1 kW
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 1 to 65000; Step: 1 kvar
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 1 to 65000; Step: 1 kVA