EasyManua.ls Logo

GE Power Quality Meter Series

GE Power Quality Meter Series
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Power Management PQM Power Quality Meter 7-63
7 MODBUS COMMUNICATIONS 7.3 MODBUS MEMORY MAP
7
7.3.5 ANALOG OUTPUT PARAMETER RANGE
Table 7–12: ANALOG OUTPUT PARAMETER RANGE FOR SERIAL PORTS (Sheet 1 of 2)
NO. ANALOG OUT PARAMETER RANGE STEP UNITS/
SCALE
DEFAULT
0 Not Used 0 0 --- 0
1 Phase A Current 0 to 150 1 % 0
2 Phase B Current 0 to 150 1 % 0
3 Phase C Current 0 to 150 1 % 0
4 Neutral Current 0 to 150 1 % 0
5 Average Phase Current 0 to 150 1 % 0
6 Current Unbalance 0 to 1000 1 0.1 x% 0
7 Voltage Van 0 to 200 1 % 0
8 Voltage Vbn 0 to 200 1 % 0
9 Voltage Vcn 0 to 200 1 % 0
10 Voltage Vab 0 to 200 1 % 0
11 Voltage Vbc 0 to 200 1 % 0
12 Voltage Vca 0 to 200 1 % 0
13 Average Phase Voltage 0 to 200 1 % 0
14 Average Line Voltage 0 to 200 1 % 0
15 Voltage Unbalance 0 to 1000 1 0.1 x% 0
16 Frequency 0 to 7500 1 0.01 xHz 0
17 *3 Phase PF –99 to +99 1 0.01 xPF 0
18 3 Phase kW –32500 to +32500 1 kW 0
19 3 Phase kvar –32500 to +32500 1 kvar 0
20 3 Phase kVA 0 to 65400 1 kVA 0
21 3 Phase MW –32500 to +32500 1 0.1 xMW 0
22 3 Phase Mvar –32500 to +32500 1 0.1 xMvar 0
23 3 Phase MVA 0 to 65400 1 0.1 xMVA 0
24 *Phase A PF –99 to +99 1 0.01 xPF 0
25 Phase A kW –32500 to +32500 1 kW 0
26 Phase A kvar –32500 to +32500 1 kvar 0
27 Phase A kVA 0 to 65400 1 kVA 0
28 *Phase B PF –99 to +99 1 0.01 xPF 0
29 Phase B kW –32500 to +32500 1 kW 0
30 Phase B kvar –32500 to +32500 1 kvar 0
31 Phase B kVA 0 to 65400 1 kVA 0
32 *Phase C PF –99 to +99 1 0.01 xPF 0
33 Phase C kW –32500 to +32500 1 kW 0
34 Phase C kvar –32500 to +32500 1 kvar 0
35 Phase C kVA 0 to 65400 1 kVA 0
36 3 Phase +kWh Used 0 to 65400 1 kWh 0
37 3 Phase +kvarh Used 0 to 65400 1 kvarh 0
*
Due to the fact that –0 and +0 both exist for power factor, the value stored in the PQM serial register is the
opposite of the value shown on the display.
Example: If the range 0.23 lead (–0.23) to 0.35 lag (+0.35) is required, –77 (–100+23)and +65 (100–35) must
be sent.

Table of Contents

Related product manuals