GE Power Management PQM Power Quality Meter 4-29
4 PROGRAMMING 4.3 S2 SYSTEM SETUP
4
4.3.5 PULSE OUTPUT
Figure 4–17: SETPOINTS PAGE 2 – SYSTEM SETUP / PULSE OUTPUT
]] SETPOINTS
]] S2 SYSTEM SETUP
]] SETPOINTS
]] S3 OUTPUT RELAYS
SETPOINT
] CURRENT/VOLTAGE
] CONFIGURATION
] SWITCH INPUT D
]
POS kWh PULSE OUTPUT
RELAY: OFF
POS kWh PULSE OUTPUT
INTERVAL: 100 kWh
Range: ALARM, AUX1, AUX2, AUX3, OFF
NEG kWh PULSE OUTPUT
RELAY: OFF
NEG kWh PULSE OUTPUT
INTERVAL: 100 kWh
POS kvarh PULSE OUTPUT
RELAY: OFF
POS kvarh PULSE OUTPUT
INTERVAL: 100 kvarh
NEG kvarh PULSE OUTPUT
RELAY: OFF
NEG kvarh PULSE OUTPUT
INTERVAL: 100 kvarh
kVAh PULSE OUTPUT
RELAY: OFF
kVAh PULSE OUTPUT
INTERVAL: 100 kVAh
PULSE WIDTH:
100 ms
Range: 1 to 65000; Step: 1 kWh
] PULSE OUTPUT
]
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 1 to 65000; Step: 1 kWh
Range: 1 to 65000; Step: 1 kvarh
Range: 1 to 65000; Step: 1 kvarh
Range: 1 to 65000; Step: 1 kVAh
Range: 100 to 2000; Step: 10 ms
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: ALARM, AUX1,
AUX2, AUX3, OFF
MESSAGE
MESSAGE
MESSAGE