EasyManua.ls Logo

gefran VDI100 Series

gefran VDI100 Series
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
03-0X =05: Multi-speed/position setting command 4 (setting =05).
Select frequency reference using multi-function digital input.
In SV or PMSV mode (00-00=3, 4), with 03-00~07 set to 51, multi-speed command can be used to select multi-
ple segment positions.
03-0X =29: Jog frequency selection (setting =29). Select frequency reference using the multi-function digital
input. In SV or PMSV mode (00-00=3, 4), with 03-00~07 set to 51, multi-speed command can be used to select
multiple segment positions.
Table4.4.7Multi-speedoperationselection
Speed
Multi-function digital input (S1 to S8) *3
Frequency selection
Jog frequency
reference
Multi-speed
frequency 4
Multi-speed
frequency 3
Multi-speed
frequency 2
Multi-speed
frequency 1
1 0 0 0 0 0 Frequency command 0( 05-01) or main speed frequency *2
2 0 0 0 0 1
Auxiliary speed frequency (04-05 = 0) or frequency refer-
ence 1 ( 05-02) *3
3 0 0 0 1 0 Frequency command 2 ( 05-03)
4 0 0 0 1 1 Frequency command 3 ( 05-04)
5 0 0 1 0 0 Frequency command 4 ( 05-05)
6 0 0 1 0 1 Frequency command 5 ( 05-06)
7 0 0 1 1 0 Frequency command 6 ( 05-07)
8 0 0 1 1 1 Frequency command 7 ( 05-08)
9 0 1 0 0 0 Frequency command 8 ( 05-09)
10 0 1 0 0 1 Frequency command 9 ( 05-10)
11 0 1 0 1 0 Frequency command 10( 05-11)
12 0 1 0 1 1 Frequency command 11 ( 05-12)
13 0 1 1 0 0 Frequency command 12 ( 05-13)
14 0 1 1 0 1 Frequency command 13( 05-14)
15 0 1 1 1 0 Frequency command 14 ( 05-15)
16 0 1 1 1 1 Frequency command 15 ( 05-16)
17 1 *1 - - - - Jog frequency command (00-18)
0: OFF, 1: ON, -: Ignore
*1. Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.
*2. When parameter 00-05=0 (frequency reference input = digital operator), multi-speed frequency 1 will be set
by 05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference input=control circuit
terminal), multi-speed frequency command 1 is input through analog command terminal AI1 or AI2).
*3. Multi-speed operation is disabled when PID is enabled.
WiringExample: Figure 4.4.17 and 4.4.18 show an example of a 9-speed operation selection.
Figure4.4.17ControlTerminalWiringExample
S1 Forward Run / Stop (03-00 = 0)
S2 Reverse Run / Stop (03-01 = 1)
24VG
S3 External Fault (03-02 = 25)
S4 Fault Reset (03-03 = 17)
S5 Multi-Step Speed Ref 1 (03-04=2)
S6 Multi-Step Speed Ref 2 (03-05=3)
S7 Multi-Step Speed Ref 3 (03-06=4)
S8 Jog Frequency Reference (03-07=29)
146 VDI100 • Instruction manual

Table of Contents

Related product manuals