Setting
Function
Contents
Control mode
Name LCD display V/f
V/f
+
PG
SLV SV
PM
SV
PM
SLV
SLV2
35 Reserved Invalid Do Func. Reserved - - - - - - -
36 Reserved Invalid Do Func. Reserved - - - - - - -
37
PID Feedback Loss
Detection Output
PID Fbk Loss ON: PID Feedback Loss O O O O O O O
38 Break Release Brake Release ON: Release Brake X X O O O X X
39
Frequency Detection
1 (dedicated for Crane)
Freq. Detect 1
(Dedicated crane)
ON: Output frequency > 03-13
Hysteresis range : 03-14
O O O X X X X
40 Frequency Output Frequency output Ing
ON: Inverter status is at DC brake, Base Block or
stop.
X X X O X X X
42 Reserved Invalid Do Func. Reserved - - - - - - -
43 Reserved Invalid Do Func. Reserved - - - - - - -
44 Reserved Invalid Do Func. Reserved - - - - - - -
45 PID sleep PID Sleep ON: During PID Sleep O O X X X X X
46 Reserved Invalid Do Func. Reserved - - - - - - -
47 Reserved Invalid Do Func. Reserved - - - - - - -
48 Reserved Invalid Do Func. Reserved - - - - - - -
49 Reserved Invalid Do Func. Reserved - - - - - - -
50 Frequency Detection 3 Freq. Detect 3
ON: output frequency > 03-44,
Hysteresis range: 03-45
O O O O O O O
51
Frequency Detec-
tion 4
Freq. Detect 4
OFF: output frequency > 03-44,
Hysteresis range: 03-45
O O O O O O O
52 Frequency Detection 5 Freq. Detect 5
ON: output frequency > 03-46,
Hysteresis range: 03-47
O O O O O O O
53 Frequency Detection 6 Freq. Detect 6
OFF: output frequency > 03-46,
Hysteresis range: 03-47
O O O O O O O
54
Turn on short-circuit
braking
SC Brk ON: Turn on short-circuit braking X X X X X O X
03-1X=0: During Running
OFF Run command is OFF and the inverter is stopped.
ON Run command is ON or output frequency is greater than 0.
03-1X=1: Fault contact output
Output is active during fault condition.
Note: Communication error (CF00, CF01) do not activate the fault contact.
03-1X=2: Frequency Agree
Output is active when the output frequency falls within the frequency reference minus the frequency detection
width (o3-14).
03-1X=3: Setting Frequency Agree
Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequen-
cy detection level (o3-13).
03-1X=4: Frequency detection 1
Output is active when the output frequency rises above the frequency detection level (03-13) + frequency de-
tection width (o3-14) and deactivates when the output frequency falls below frequency detection level (o3-13).
03-1X=5: Frequency detection 2
Output is active when the output frequency is below the frequency detection level (03-13) + frequency detection
width (03-14) and turns off when the output frequency falls below frequency detection level.
Refer to table 4.4.9 for the operation of frequency detection.
03-1X=6: Automatic restart.
Output is active during an auto-restart operation.
03-1X=9: Baseblock (B.B.)
Output is active when the inverter output is turned off during a Baseblock command.
03-1X=12: Over torque detected (Normally Open)
Output is active during an over torque detection see parameters 08-13 ~ 08-16.
03-1X=25: Low torque detected (Normally Open)
VDI100 • Instruction manual 157