Output is active during low torque detection see parameters 08-17 ~ 08-20.
03-1X=13: Current Agree
When output current > 03-15 and output current > 03-15 duration >03-16, it is ON.
03-1X=18: PLC status (setting =18)
Output is active when operation command parameter (00-02) is set to 3: PLC Control.
03-1X=19: PLC control contact
Output is controlled by the PLC logic
03-1X=20: Zero-speed
Output is active during zero-speed
Attive Output frequency ≥ minimum output frequency (01-08, Fmin)
OFF Output frequency is ≤ the minimum output frequency
Figure4.4.26Zero-speedoperation
t
t
ONOFF
01-08(Fmin)
Output
Frequency
Zero
Speed
03-1X=21: Inverter Ready
Output is active when no faults are active and the inverter is ready for operation.
03-1X=22: Undervoltage Detection
Output is active when the DC bus voltage falls below the low voltage detection level (07-13).
03-1X=23: Source of operation command
Output is active in local operation command.
OFF Remote mode:
00-02 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is
OFF.
SEQ LED of the keypad is ON.
ON Local mode:
00-02 = 0, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is
active.
SEQ LED of the keypad is OFF.
03-1X=24: Source of frequency command
Output is active in local frequency command.
OFF Remote mode:
00-05 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is
OFF.
REF LED of the keypad is ON.
ON Local mode:
00-05 = 0, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is
active.
REF LED of the keypad is OFF.
03-1X=26: Frequency reference missing
Output is active when the frequency reference is lost. When parameter 11-41 is set to 0 the inverter will decel-
158 VDI100 • Instruction manual