03-14 Frequency detection width
0.1~25.5 Hz
Frequency detection Level: set the multi-function output terminals R1A-R1C, R2A-R2C or PH1 (03-11, 03-12 or
03-28) to the desired detection level and bandwidth for use with multi-function output functions 2 to 5.
The time charts for the Frequency Agree Detection operation are shown in the following table 4.4.9.
Code Parameter Name / Range
03-44 Frequency Detection Level 2
0.0~599.0 Hz
03-45 Frequency Detection Width 2
0.1~25.5 Hz
03-46 Frequency Detection Level 3
0.0~599.0 Hz
03-47 Frequency Detection Width 3
0.1~25.5 Hz
Frequency Detection: Set R1A-R1C R2A-R2C or PH1 (03-11, 03-12 or 03-28) to output frequency signal and
then set frequency conrmation and output frequency detection 1~6.
Please refer table 4.4.9.detection operation of frequency time block
Table4.4.9Frequencydetectionoperation
Function Detection operation of frequency confirmation Description
Frequency agree
time
time
ONOFF
FWD
REV
03-14
03-14
Freq
Reference
Output
Frequency
Frequency
Agree
Signal
ON
Freq
Reference
Output is active when the output frequency falls within the frequen-
cy reference minus the frequency detection width (03-14).
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 3 (Frequency agree).
Set frequency
agree
time
time
ONOFF
FWD
REV
03-14
Output
Frequency
Setting
Frequency
Agree
Signal
ON
03-13
03-13
03-14
Output is active the output frequency falls within the frequency
detection width (03-14) of the set frequency detection level (03-13).
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 3 (Set frequency agree).
Output frequency
detection 1
ON ONOFF OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output frequency rises above the fre-
quency detection level (03-13) + frequency detection width (o3-14)
and deactivates when the output frequency falls below frequency
detection level (03-13).
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 4 (Output frequency detection 1).
160 VDI100 • Instruction manual