Fault of door movement
Fault description Fault correction
F.
Display alternates between F and number
5.5
Connection to digital limit
switch (DES) could not be
established.
Check plug and connecting cable of DES
5.6
Fault in door movement,
exceeding the movement
duration
Check door drive unit for stalling.
Danger of the door dropping!
Stalling may indicate a catch incident.Take
appropriate measures.
Check the door mechanism for damage.
Check limit switch turn.
ChecknallimitpositionOPEN.Whenthe
doorhitsacushion,thencorrectthenallimit
position.
Check brake.
5.7
Fault in rotating direction Establishclockwiserotatingeldatthepower
connection.
Reset door control to factory setting (
9.5).
All settings will be lost!
5.8
Inadmissible door
movement from idle state.
Checkbrakeandrectierondoordriveunit.
For doors with counter-balancing only: check
spring balance.
5.9
Door drive unit does not
follow the given direction
of movement.
Check motor connection.
Check brake.