EasyManua.ls Logo

GFA DC 8010 - Page 54

GFA DC 8010
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50
Frequency inverter fault
These fault indications appear only for door drive units with
with frequency inverter.
Fault description Fault correction
F.
Display alternates between F and number
6.1
▪ Closing speed is too high ▪ Checkdoormechanismforsti󰀨ness.
▪ For doors with counter-balancing only: check
for spring breakage.
▪ Replace door drive unit if necessary.
6.2
▪ Internal communication
fault of frequency inverter
▪ Switchdoorcontrolo󰀨andon.
▪ Check connecting cable to limit switch.
▪ Replace door drive unit if necessary.
6.3
▪ Undervoltage in DC
voltage link
▪ Measure voltage during door movement.
▪ Measure grid input voltage.
▪ Change ramp times / speeds (
4.1-4.9)
6.4
▪ Overvoltage in DC voltage
link
▪ Measure voltage during door movement.
▪ Measure grid input voltage.
▪ Change ramp times / speeds (
4.1-4.9)
6.5
▪ Temperature limit
exceeded
▪ Door drive unit overloaded.
▪ Check for excessive ambient temperature.
▪ Allow door drive unit to cool down and reduce
number of cycles.
6.6
▪ Permanent current
overload
▪ Door drive unit overloaded.
▪ Checkdoormechanismforsti󰀨ness
6.7
▪ Fault of brake / frequency
inverter
▪ Check brake.
▪ Replace door drive unit if necessary.
6.9
▪ Collective indication
Frequency inverter
▪ Switchdoorcontrolo󰀨andon.
▪ Replace door drive unit if necessary.

Table of Contents