50
Frequency inverter fault
These fault indications appear only for door drive units with
with frequency inverter.
Fault description Fault correction
F.
Display alternates between F and number
6.1
Closing speed is too high Checkdoormechanismforsti󰀨ness.
For doors with counter-balancing only: check
for spring breakage.
Replace door drive unit if necessary.
6.2
Internal communication
fault of frequency inverter
Switchdoorcontrolo󰀨andon.
Check connecting cable to limit switch.
Replace door drive unit if necessary.
6.3
Undervoltage in DC
voltage link
Measure voltage during door movement.
Measure grid input voltage.
Change ramp times / speeds (
4.1-4.9)
6.4
Overvoltage in DC voltage
link
Measure voltage during door movement.
Measure grid input voltage.
Change ramp times / speeds (
4.1-4.9)
6.5
Temperature limit
exceeded
Door drive unit overloaded.
Check for excessive ambient temperature.
Allow door drive unit to cool down and reduce
number of cycles.
6.6
Permanent current
overload
Door drive unit overloaded.
Checkdoormechanismforsti󰀨ness
6.7
Fault of brake / frequency
inverter
Check brake.
Replace door drive unit if necessary.
6.9
Collective indication
Frequency inverter
Switchdoorcontrolo󰀨andon.
Replace door drive unit if necessary.