The battery stop charging once the battery SOC reaches Charge Cut-off
SOC.
To set the stop SOC for battery discharge, please refer to section 9.4.4
Setting the Battery Parameters and set the Depth of Discharge
(On Grid) and Depth of Discharge (Off Grid) through the LCD screen.
When selecting the safety regulation country/region, the system will
automatically configure the overvoltage and undervoltage protection,
overfrequency and underfrequency protection, inverter on-grid
voltage/frequency, connection slope, Cosφ curve, Q(U) curve, P(U) curve, FP
curve, high and low voltage ride-through, etc. according to the safety regulation
requirements of different regions.
The generation efficiency of inverter differs in different working modes. Please
set according to the local actual electricity consumption.