6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 29
Control Panel Installation
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4.5.
Figure 4.5 Splicing Control Panel Battery Cable to RBB Battery Cable Extenders
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4.6.
Figure 4.6 Battery Connections in the RBB Cabinet
4. Connect battery leads to the backup battery terminals. See Figure 4.6. Observe the proper polarity to prevent damage to the batteries
or the control panel.
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4.6). Screw the cover screw ¾ of the way into the cover
mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4.7.
Figure 4.7 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws.
NOTE: Figure 4.6 is an example of how the wire connections can be routed. However, any other cabinet knock-outs (on either the main
control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets.
Cover Plate
Mounting Keyholes