47
1. Under Controller and Programming, select Configure Controller
Redundancy.
2. Select Enable Controller Redundancy, and then click OK.
The configuration of I/O modules in the rack local to the
controller will be removed and a static IP address must be
configured for the secondary controller.
3. Configure the IP address of the controllers.
l If the Obtain an IP Address Automatically options of ETH1 and
ETH2 were enabled, this option will be disabled automatically.
Configure Primary Controller IP Address and Secondary Controller
IP Address manually.
l If the Obtain an IP Address Automatically options of ETH1 and
ETH2 were disabled, configure the Secondary Controller IP
Address manually.
Configuring an I/O module
Configure an I/O module for ControlEdge 900
controller
1. From the Home Page, under I/O and Communications and click
Configure Modules > Configure I/O Modules.
2. Click Add I/O Module, the Add I/O Module dialog appears.
3. Select the Type, assign the Rack and Slot, and set the IOM Scan Time
for the Module.
4. Click OK to add the I/O module.
5. Select the corresponding I/O module, configure I/O channels.
Configure an I/O module for ControlEdge 2020
controller
You can configure onboard I/O modules, expansion I/O modules and
a third party I/O ST103A for ControlEdge 2020 controller.
To configure an onboard I/O
1. From the Home Page, under I/O and Communications and click
Configure I/O.
Chapter 4 - Software