EasyManuals Logo

Honeywell DR4311 User Manual

Honeywell DR4311
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #177 background imageLoading...
Page #177 background image
Troubleshooting and Pen Alignment
of Recorder without Display
4/00 DR4300 Circular Chart Recorder Product Manual 165
7.3.2 Recorder Failure Troubleshooting
Procedure
Table 7-2 explains how to troubleshoot recorder failure symptoms.
Table 7-2 Troubleshooting Recorder Failure Symptoms
Step What to do How to do it or
where to find the instructions
1
Check the supply voltage. Measure the line voltage across the line and neutral
connections at TB1 on the printed circuit assembly
(PCA) on the right (for pen 1).
2
Check the connections to TB1 on the
pen 1 PCA.
Refer to ac wiring procedures in Section 2 –
Installation.
3
Check the system for brown-outs,
heavy load switching, etc.; and
conformance to installation
instructions.
Refer to Section 2 – Installation.
4
Replace the PCA for pen 1. Refer to the replacement procedures in Section 9 –
Replacing Hardware Assemblies.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DR4311 and is the answer not in the manual?

Honeywell DR4311 Specifications

General IconGeneral
BrandHoneywell
ModelDR4311
CategoryVoice Recorder
LanguageEnglish

Related product manuals