Appendix D - Using Accutune II
4/00 DR4300 Circular Chart Recorder Product Manual 229
D.3 Using Accutune with Duplex (Heat/Cool) Control
Introduction
TUNE can be done for applications using Duplex (Heat/Cool) control.
During tuning, Accutune II assumes SP 1 will cause a Heating demand, and then the calculated tuning
parameters will be automatically entered as the first set of PID constants. Likewise, it assumes tuning at
Local SP 2 will cause a Cooling demand, and the cooling parameters will be entered as the second set of
PID constants.
Procedure
After TUNE has been enabled in the tuning set up group as described in Section 4, use the procedure in
Table D-2 to start tuning. Note that control group parameter NumSPs must be set to TWO to enable
the second setpoint.
To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode. The
message AbRT (abort) will be displayed as the value of tuning set up group parameter AT ERR. The
tuning parameters will retain the values they had at the start of the Accutune operation.
Table D-2 Procedure for Using Accutune for Duplex Control
Step Press Action/Result
Heating Tuning
1
DISP
until you see
Lower Display
SP nnn
Display Setpoint 1.
2
or
Until the value of Setpoint 1 is at the desired value within the Heat
zone.
Make sure the recorder is in Auto mode. (“A” indicator lit.)
If not, use the MAN/AUTO/RESET key to put the unit in Auto.
3
DISP
until you see
Lower Display
UseSPn
This is the prompt used to select the setpoint. If
it is not USESP1, use or to switch to USESP1”.
4
DISP
until you see
Lower Display
TuneOF
If TuneOF (tune off) does not appear, then
Accutune is not enabled.
5
or
to toggle to
Lower Display
TuneON
Tuning will begin and the lower display will flash
TUNING. The output will cycle between 50 %
and 100 % (or high output limit). When tuning
has been completed the lower display will again
show TuneOF. The Heat tuning parameters are
entered for the first set of PID constants in the
tuning set up group.