DR4300 Circular Chart Recorder
210 DR4300 Circular Chart Recorder Product Manual 4/00
Calibration Range 1 Range 2 24 HR
P/N 24001660-XXX
7 DAY
P/N 24001661-XXX
Linear PSI/Linear GPM 0 to 15 0 to 7800 204
J T/C Deg. F/Linear 0 °F to 600 °F 0 to 2000 PSI 647*
0 °F to 300 °F 0 to 100 617* 617*
0 °F to 300 °F 0 to 400 656*
0 °F to 400 °F 0 to 100 124*
0 °F to 400 °F 0 to 800 629*
0 °F to 600 °F 0 to 100 611*
0 °F to 300 °F 0 to 500 636*
J T/C Deg. C/K T/C Deg. C 0 °C to 300 °C0 °C to 1200 °C 143*
–18 °C to +315 °C –18 °C to
+1315 °C
112*
J T/C Deg. F/J T/C Deg. C 95 °F to 455 °F 35 °C to 235 °C 026* 026*
J T/C Deg. F/K T/C Deg. F 0 °F to 300 °F0 °F to 1500 °F 186
0 °F to 600 °F0 °F to 2400 °F 604*
K T/C Deg. F/J T/C Deg. F 1300 °F to 2000 °F 400 °F to 800 °F 649*
0 °F to 300 °F0 °F to 1600 °F 651*
K T/C Deg. F/Linear –100 °F to +900 °F 0 to 10 635*
0 °F to 2000 °F 0 to 2 163*
500 °F to 2000 °F 0 to 1.5 127*
T T/C Deg. C/Linear –87 °C to +191 °C 0 to 100 153*
T T/C Deg. F/Linear 50 °F to 250 °F 0 to 100 643*
–50 °F to +300 °F 0 to 100 631*
T T/C Deg. C/Linear –100 °C to
+100 °C
0 to 100 162*
–80 °C to +180 °C 0 to 100 657*
RTD Deg. F/Linear 100 °F to 300 °F 0 to 160 152*
RTD Deg. C/Linear –5 °C to +50 °C 0 to 100 102*
–10 °C to +60 °C 0 to 100 616*
–35 °C to +75 °C 0 to 100 101*
–76 °C to +100 °C 35 to 0 607*
–50 °C to +100 °C 0 to 100 638* 638*
–76 °C to +100 °C 35 to 0 607*
–75 °C to
+1800 °C
35 to 0 608*