Model IFP-2100/ECS Installation Manual LS10143-001SK-E
12-3
OPG Inhibit Trouble Restore FJ Group # +
1000
FJNN001GGG 3 320 00 Group #
OPG Inhibit of Releasing Group SS Group # +
1000
SSNN001GGG 1 203 00 Group #
OPG Inhibit of Releasing Group
Restore
SR Group # +
1000
SRNN001GGG 3 203 00 Group #
Phone line 1 trouble detected LT 1 LTNN000001 1 351 00 000
Phone line 1 trouble restore LR 1 LRNN000001 3 351 00 000
Phone line 2 trouble detected LT 2 LTNN000002 1 352 00 000
Phone line 2 trouble restore LR 2 LRNN000002 3 352 00 000
Printer is off-line trouble VZ Exp. ID VZNNXX0000 1 336 Exp. ID 000
Printer is off-line trouble restore VY Exp. ID VYNNXX0000 3 336 Exp. ID 000
Printer is out of paper trouble VO Exp. ID VONNXX0000 1 335 Exp. ID 000
Printer is out of paper trouble re-
store
VI Exp. ID VINNXX0000 3 335 Exp. ID 000
Releasing Notif/Control Circuit
Disabled
pi Exp. ID SS Point # SSNNXXPPPP 1 203 Exp. ID Point #
Releasing Notif/Control Circuit
enabled
pi Exp. ID SR Point # SRNNXXPPPP 3 203 Exp. ID Point #
Remote programming aborted or
ended with errors
RU 0 RUNN000000 1 413 00 000
Remote programming ended nor-
mally
RS 0 RSNN000000 1 412 00 000
Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103
Repeater ground fault trouble re-
store
EN 0103 ENNN000103 3 334 Panel ID 103
Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100
Repeater missing trouble restore EN 0100 ENNN000100 3 334 Panel ID 100
Repeater Rx1 communication
trouble
EM 0101 EMNN000101 1 334 Panel ID 101
Repeater Rx1 communication
trouble restore
EN 0101 ENNN000101 3 334 Panel ID 101
Repeater Rx2 communication
trouble
EM 0102 EMNN000102 1 334 Panel ID 102
Repeater Rx2 communication
trouble restore
EN 0102 ENNN000102 3 334 Panel ID 102
SBUS Class A supervision lost ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS Class A supervision re-
store
ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2100/ECS
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code