Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019 36
SB-ECM Module System Components
3.7 SB-ECM Module
This module can control an automatic extinguishing/release system. The module controls eight (8)
supervised inputs with safety-related functions, four (4) safety related supervised outputs to control
solenoids, two (2) non-safety related supervised outputs to control notification appliances and one
(1)virtual output V15, used to activate the automatic release sequence in embedded mode or as an
internal variable in I/O mode. As to the 8 input channels, the first six are suitable for NO/NC con-
tacts with a max line current of 40mA, while the last two channels are suitable for controlling
NO/NC or conventional smoke detector contacts with a max line current of 130mA. As for the 6
output channels, the first four channels are suitable for controlling solenoid valves or visual/acous-
tic signals with a max current of 500mA and safety-related functions, while the last two channels
are regulate NAC outputs with a max current of 195 mA.
Note: Synchronization of devices between zones or within a zone is not permissible using this mod-
ule.
3.7.1 Technical Specifications
Number of input channels: 8 individually configurable
Wiring:
Inputs
Class B, Style B and Style C
Outputs (NAC)
Class B, Style Y
Outputs (REL)
Class B
Alarm threshold for input channels 1-6: 2 programmable thresholds from 4 to 35mA
Alarm threshold for input channels 7-8: 2 programmable thresholds from 4 to 120mA
Short circuit threshold for input channels 1-6: programmable from 4 to 40mA *
Short circuit threshold for input channels 7-8: programmable from 4 to 131mA *
Open Circuit threshold for input channels 1-8: 1mA
Input channel test: performed every 30 seconds
Max current for output channels 9-12: 500 mA
Short circuit threshold for output channels 9-12: current >0.75-1.5 A
Open Circuit threshold for output channels 9-12: current <0.5-9.5 mA
Channel test for outputs 9-12: performed every 3 seconds
Max current for output channels 13-14: 195 mA
Max. Line Impedance Channels 13-14: 50 ohms
Fuse trip current for channels 13-14: >600 mA
Power supply voltage: 24VDC
Current consumption in stand by: 159 mA
Operating temperature:
0 to 49 °C (32 to 120.2 °F)
Storage temperature:
-55 to 85 °C (-67 to 185°F)
Max humidity: 0-95% non condensing
Protection rating: IP30
Mounting: T35 DIN rail
Dimensions:
53 x 167 x 100 (W x H x D mm) (2.1” x 6.6” x 4”)
Weight: approx. 600g (21 oz.)
Connections: 2.5mm² removable terminal blocks
Max. Line impedance SLC: 20 ft (6.096 m) in the same room, in conduit
Max. Line Impedance Input Channels 1-8: 50 ohms
Ground Fault impedance: </ 500 ohms
Max distance between two modules: 20 ft (6.096 m) in conduit
*For compliance with UL 864, the short circuit threshold for channels 1-6 should be between 4mA and 35mA. The
short circuit thresholds for channels 7 and 8 should be between 4mA and 125mA