37 ST 800 Pressure Transmitter User’s Manual Revision 15
Note: Sets loop output to low
saturation when the
differential pressure is below -
10% Flow.
Breakpt (%Flow)
(Available only
when Transfer
Function is
Square Root)
Enter the low flow cutoff
point when Single Breakpt or
Zero Flow is selected. Range:
0.0 to 25.0 %Flow.
Press to enter
menu selection. Press
and to select
number. Press to
enter and shift to
next
digit.
The limit for the Lower Range
Value is 2X the Lower Range
Limit (LRL) of the Meter Body
The limit for the Upper Range Value
is 2X the Upper Range
Limit (URL) of the Meter Body
ATTENTION: Executing this service will set the
Lower Range Value (LRV) equal to the input pressure.
Press to
enter menu
selection
to execute
ATTENTION: Executing this service will set the
Upper Range Value (URV) equal to the input pressure.
Press to
enter menu
selection
to execute
Select the current month.
Enter the day of the month.
Press ENTER to write the HART Date to the
transmitter.