39 ST 800 Pressure Transmitter User’s Manual Revision 15
The sampling window of
PILD in minutes, which
determines the cycle of
PILD runs for both
training and monitoring
mode.
Enter the sample window
Value.
Range: 3 mins,
6 mins, 9 mins, 12 mins,
15 mins.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and shift
to next digit.
PILD
(Available only
if the PILD
option is
enabled)
The up limit of PILD
factor for normal status...
Enter the Up Limit Value.
Range: 0.50 to 1.00.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and shift
to next digit
The Down limit of PILD
factor for normal status...
Enter the Down Limit
Value.
Range: Both Limit to 0.50
See Note below.
Press to enter
menu selection
and to select
number.
to enter and shift
to next digit
The Both sides blockage
limit of PILD.
Enter the Both Limit Value.
Range: 0.00 to Down
Limit.
It is applicable for only DP
transmitter.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and shift
to next digit
The High Pass Filter
(HPF) Cut off Frequency
(f
0
) reduces noise
fluctuations in the PILD
Factor measured value.
Enter the HPF f0 Value.
Range: 0.0 to 5.0.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and shift
to next digit
Note:
This parameter will be “Read Only” when the user configures PILD as Enabled in this sub menu. An attempt to
configure this parameter will then invoke the pop-up message “Read Only! PILD Active”. The parameters Up
Limit, Down Limit and Both Limit are available to change in Monitoring mode while PILD is enabled. An attempt
to change these parameters in Training mode results in the pop-up "Read Only! Training Mode".