63 ST 800 Pressure Transmitter User’s Manual Revision 15
SP Reset Correct
[25SPRST]
Executing this selection resets
Static Pressure Zero to the
factory value of 0.
Press to
enter menu
selection
Press to
initiate action
Barometric Standard
[26BARSTD]
Enter an atmospheric pressure
value corresponding to a
barometric standard.
If the difference between the
measured atmospheric pressure
and the user- entered
barometric standard pressure is
> 1 psi (27.680672 inH2O
[4°C]) the
calibration will not be performed.
Range: 330-490 inH2O [4°C]
Default: 406.782 inH2O [4°C]
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit to
the right
Barometric Correct
[27BARCOR]
One point field offset
Calibration Method for AP
transmitters only
Adjusts the pressure measured
by the AP transmitter with the
user entered barometric
standard.
Press to
enter menu
selection
Press to
initiate action
Calibrate High Point
[28CAL HI]
Cal high point value in inH2O
[4°C]
Range: LRV to URV
Default: URV
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit
to the right
Calibrate Low Point
[29CAL LO]
Cal low point value in inH2O
[4°C]
Range: LRV to URV
Default: LRV
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit
to the right