Page 94 ST 800 Series HART/DE Option User’s Manual Revision 5.0
(continued)
Non-Critical
The SPAN correction factor is outside acceptable
limits. INPUT may have been incorrect during
calibration or transmitter was in output mode
during a URV CORRECT procedure.
Resolution:
Check input pressure and be sure that it matches
calibrated range values (LRV and URV). Check
Meter Body. Perform an LRV or ZERO
CORRECT procedure followed by a URV
The ZERO correction factor is outside acceptable
limits. INPUT may have been incorrect during
calibration or transmitter was in output mode
during an LRV or ZERO CORRECT procedure.
Resolution:
Check input pressure and be sure that it matches
calibrated range values (LRV and URV). Check
Meter Body. Perform an LRV or ZERO
CORRECT procedure followed by a URV
Temperature
Meter Body temperature is too high. Accuracy
and life span may decrease if it remains high.
Resolution:
Verify the environment temperature is within
specification. Take steps to insulate Meter Body