Page 76 ST 800 Series HART/DE Option User’s Manual Revision 5.0
8 HART Advanced Diagnostics
8.1 About This Section
This section provides information about the Advanced Diagnostic features in the ST 800 SmartLine
Pressure Transmitter.
8.2 Advanced Diagnostics
Table 14Viewing Advanced Diagnostics
What you want to view What to do
Install date
PV (Process Variable) Tracking
Diagnostics
SV (Meter Body Temperature )Tracking
Diagnostics
TV (Static Pressure) Tracking
Diagnostics (DP transmitters only)
ET (Electronics Temperature) Tracking
Diagnostics
Stress Life
Service Life
Operating Voltage Tracking Diagnostics
AVDD (Sensor Supply Voltage)
Tracking Diagnostics
Sensor CPU Temp. Tracking
Power Up Diagnostics
Plugged Impulse Line Detection (PILD)
Select Start/FDC to Launch the FDC application
on the MC Toolkit.
On the Home page, select Online and establish
connection with the device.
Select My Device\Diagnostics\Adv Diagnostics.
Plugged Impulse Line Detection (PILD)
An advanced diagnostic function Plugged Impulse Line Detection (PILD) becomes available in
ST800 SmartLine Pressure Transmitters (R300.3) in Differential Pressure (DP) transmitters,
Absolution Pressure (AP) transmitters and Gauge Pressure (GP) transmitters.
PILD is a powerful tool to detect when the impulse lines are blocked by solids or frozen fluid in
process. Alarms on impulse line blockage will allow users to take proper measures at an early point of
time so that effect of false readings from transmitters on process control can be minimized. See
HART transmitter parameters, Table 11 on page 33 .
Install Date
Install Date
Parameter
Description
Date of device installation. Date displayed in mm/dd/yyyy
format where mm=month, dd=day, yyyy=year
Set-up
User enters a date once during device lifetime. Once
date is entered no further updates are possible and value
becomes read only and is permanently saved.