Page 84 ST 800 Series HART/DE Option User’s Manual Revision 5.0
Power Up Diagnostics
Table 26Power Up Diagnostics
Pwr fail
counter
Parameter Description Total number of power-ups
experienced by the unit.
Set-up
None initialized to zero prior to
leaving factory.
NVM
Backup once each 8 hour period
Note
Only one power failure in each 8 hour
period is counted.
Time since
last power fail
Method
Description
Displays time since last power-up in
minutes.
Set-up
None.
NVM
Backup once each 8 hour period
PILD Status
Name Description
PILD Functionality
Status
PILD Status
For DP transmitters possible statuses are:
both sides blocked
one side blocked.
Not Blocked
For AP/GP transmitters possible statuses are:
Blocked
Not blocked
PILD factor
PILD factor for prediction.
Possible values are 0.0 to 1.00 to the second decimal
places.
Current Mode Current Work Mode
If PILD is enabled, modes are:
Training
Monitoring
If PILD is disabled,
no output.