Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 83
AVDD Tracking Diagnostics
Table 23 – Maximum and Minimum AVDD Tracking
Max AVDD Parameter Description Maximum Sensor Supply Voltage
experienced by device since last reset
of voltage parameters.
AVDD Up
Displays time since last Sensor
Supply Voltage was above last Max
Minimum Sensor Supply voltage
experienced by device since last reset
of voltage parameters.
Time since Last
AVDD Down
Method Description Displays time since last Sensor
Supply Voltage was below last Min
Sensor CPU Temperature Tracking Diagnostics
Table 24 – Maximum Sensor CPU Temperature Tracking
Temp.
Maximum Sensor CPU Temperature
experienced by device
Upper Stress
Limit
Accumulation of minutes that Sensor
CPU Temperature has been above
the value of Max Sensor CPU Temp.
Backup once each 8 hour period
Sensor CPU
Temp. Up
Time that has passed since the last
time Sensor CPU Temp. has passed
above the value of “Max Sensor CPU
Temp” (in days, hours and minutes).
Backup once each 8 hour period
Table 25 – Minimum Sensor CPU Temperature Tracking
Temp.
Minimum Sensor CPU Temperature
experienced by device
Upper Stress
Limit
Accumulation of minutes that Sensor
CPU Temperature has been below
the value or Min Sensor CPU Temp.
Backup once each 8 hour period
Sensor CPU
Temp. Down
Time that has passed since the last
time Sensor CPU Temperature has
passed below the value of “Min
Sensor CPU Temp” (in days, hours
NVM Backup once each 8 hour period