Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 59
For the input calibration procedure, current loop component tolerances and values are
not critical if they support reliable communication between the Transmitter and the MC Toolkit.
However, the
Transmitter must be level
, because the meter body contains fluids that can
affect zero sensing. For leveling proceures. Refer to the ST 800 SmartLine Transmitter User’s
Manual, 34-ST-25-35, “Mounting Transmitters with Small Absolutge or Differential Pressure
Spans” for information on Transmitter leveling.
For the input calibration procedures, connect the test setup illustrated in. Either voltage mode
(Voltmeter across the resistor) or current mode (Ammeter in series with the resistor) is satisfactory.
Figure 11Input Calibration Connections
6.8 Input Calibration Procedure
Correct the Input at Zero
1. Start the MC Toolkit application. Establish communication between the Transmitter and the
MC Toolkit.
2. From the DE MAIN MENU, select Configure to call up the DE CONFIGURE display.
3. From the DE CONFIGURE display: