Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 89
Status Type
(HART Command
Details/Resolutions
(continued)
Non-critical status
(Warning)
• Sensor Overload/Sensor Fault
• Redundant Characterization Calculation
Error
• Calculated pressure is above Upper
Transducer Limit (UTL).
Resolution:
Check range and, if required, replace transmitter
with one that has a wider range. Meter Body may
have been damaged. Check the transmitter for
accuracy and linearity. Replace Meter Body and
recalibrate if needed.
Output current is fixed and not varying with applied
input. Loop current mode is disabled or Loop Test is
active.
Resolution:
Enable Loop Current Mode if it is disabled or exit the
Loop Test mode if active.
Temperature
Meter Body temperature is too high. Accuracy and life
span may decrease if it remains high.
Resolution:
Verify the environment temperature is within
specification. Take steps to insulate Meter Body from
temperature source.
Correct
ZERO or SPAN correction factor is outside acceptable
limits. INPUT may have been incorrect during
calibration or transmitter was in output mode during a
CORRECT procedure.
Resolution:
Check input pressure and be sure that it matches
calibrated range values (LRV and URV). Check Meter
Body. Perform an LRV or ZERO CORRECT
procedure followed by a URV CORRECT procedure.
Display Failure Possible causes:
The Display has been disconnected or configuration
data has been corrupted.
Resolution:
Secure Display connections and recheck. If problem
persists, reset the device. If the problem still persists,
replace the Display