Specifications 76
Three-phase power (North America/Japan)
Specification
HP BladeSystem
c7000 Power Supply
HP 2400W High
Efficiency Power Supply
HP BL7000 2400W
Platinum Power Supply
Power cords (2)
NEMA L15-30p 2.44 m
(10 ft)
NEMA L15-30p 2.44 m
(10 ft)
NEMA L15-30p 2.44 m (10
ft)
Output
2250 W per phase 2450 W per phase 2450 W per phase
Input requirements
Rated input voltage
200 VAC to 208 VAC
line to line
115 V to 120 V line to
neutral
3-phase delta
200 VAC to 208 VAC line
to line
115 V to 120 V line to
neutral
3-phase delta
200 VAC to 208 VAC line to
line
115 V to 120 V line to neutral
3-phase delta
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current
per line cord
22.6 A at 200 VAC
21.8 A at 208 VAC
20.6 A at 220 VAC
24 A at 200 VAC
23.2 A at 208 VAC
21.8 A at 220 VAC
22.9 A at 200 VAC
22 A at 208 VAC
20.8 A at 220 VAC
Maximum input power per
line cord
7836 VA 8310 VA 7845 VA
Three-phase power (International)
Specification
HP BladeSystem
c7000 Power Supply
HP 2400W High
Efficiency Power Supply
HP BL7000 2400W
Platinum Power Supply
Power cords (2)
IEC-309 200/346-V to
240/415-V, 5-pin,
16-A
2.44 m (10 ft)
IEC-309 200/346-V
to 240/415-V, 5-pin,
16-A
2.44 m (10 ft)
IEC-309 200/346-V
to 240/415-V, 5-pin, 16-A
2.44 m (10 ft)
Output
2250 W 2450 W 2450 W
Input requirements
Rated input voltage
346 VAC to 415 VAC
line-to-line*
200 VAC to 240 VAC
line-to-neutral
3-phase WYE
346 VAC to 415 VAC
line-to-line*
200 VAC to 240 VAC
line-to-neutral
3-phase WYE
346 VAC to 415 VAC
line-to-line*
200 VAC to 240 VAC
line-to-neutral
3-phase WYE
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current
per line cord
13.1 A at 200 VAC
11.9 A at 220 VAC
10.9 A at 240 VAC
13.85 A at 200 VAC
12.6 A at 220 VAC
11.5 A at 240 VAC
13.2 A at 200 VAC
12 A at 220 VAC
11 A at 240 VAC
Maximum input power per
line cord
7836 VA 8310 VA 7845 VA
*Rated 200 VAC to 240 VAC line-to-neutral. The enclosure will not operate from higher line-to-line voltage with the WYE
wall plug configuration. Input AC modules are configured to provide 200 VAC to 240 VAC to the power supplies in this
system.

Table of Contents

Other manuals for HP BladeSystem c7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP BladeSystem c7000 and is the answer not in the manual?

HP BladeSystem c7000 Specifications

General IconGeneral
BrandHP
ModelBladeSystem c7000
CategoryEnclosure
LanguageEnglish

Related product manuals