HPE 800W Flex Slot -48VDC Hot plug Low Halogen Power SupplyHPE 800W Flex Slot -48VDC Hot plug Low Halogen Power Supply
SpecificationSpecification ValueValue
Input requirementsInput requirements
Rated input voltage -40 VDC to -72 VDC
-48 VDC
Rated input current 24 A at -40 VDC
Rated input power (W) 874 W at -40 VDC
Rated input power (BTUs per hour) 2983 at -40 VDC
Power supply outputPower supply output
Rated steady-state power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power 800 W at 200 VAC to 277 VAC
800 W at -40VDC to -72 VDC
WARNING: WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit
has no direct connection to a primary circuit and derives its power from a transformer,
converter, or equivalent isolation device.
The branch circuit overcurrent protection must be rated 27 A.
CAUTION: CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is
connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment
that has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and
also the point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the
point of connection of the earthing electrode conductor.
HPE 800W Flex Slot -48VDC Hot plug Low Halogen Power Supply 249