Troubleshooting 100
o
Parallel UPS configurationSee "Powering up the parallel system (on page 39)."
6. Contact a qualified electrician to check the power cord connections.
UPS does not provide the expected backup time
Action:
1. Be sure that the battery circuit breakers are in the On position.
2. Allow the UPS batteries to charge for 48 hours.
3. If the condition persists, contact an HP authorized service representative.
UPS does not transfer to Auto-Bypass mode
Action:
Verify the bypass utility. The UPS is receiving bypass utility power that might be unstable or in brownout
conditions.
Be sure that the Usage of Bypass user setting is enabled. For more information, see "Changing user
settings (on page 68)."
UPS is on battery
Possible cause: A utility failure has occurred, and the UPS is in Battery mode (on page 66).
Action: The UPS is powering the equipment with battery power. Save files and shut down connected
equipment.
UPS is on bypass
Possible Cause: The UPS is in Auto-Bypass mode (on page 66).
Action:
The equipment transferred to bypass utility power. Battery mode (on page 66) is not available and the
equipment is not protected; however, the utility power continues to be passively filtered by the UPS.
Check for one of the following alarms:
Overtemperature
Overload
UPS failure
Hot swap
REPO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R1500 - UPS XR and is the answer not in the manual?

HP R1500 - UPS XR Specifications

General IconGeneral
TopologyLine Interactive
Input ConnectionIEC 320 C14
Battery TypeSealed Lead Acid (SLA)
Form FactorRackmount
Nominal Output Voltage230V
Nominal Input Voltage230V
Input Frequency50/60 Hz
Typical Backup Time at Full Load5 minutes
Transfer Time4-8 ms
Hold-up Time10 ms
Input Voltage Range160 - 286 VAC
Interface PortUSB
Battery Recharge Time3 hours
Communication PortsUSB
WaveformSine wave