Troubleshooting 95
On
On1 beep
every 3 seconds
Overload
("Overload
condition" on page
98)
On
On1 beep
every 3 seconds
Overtemperature
("Overtemperature
condition" on page
98)
On
On1 beep
every 3 seconds
Site Wiring Fault
("Site wiring
condition" on page
99)
For the location of individual LEDs, see "UPS front panel LED indicators (on page 9)."
Silencing an audible alarm
To silence an alarm, press any button on the front panel display to silence the alarm. If the alarm status
changes, the alarm beeps again, overriding the previous alarm silencing.
IMPORTANT:
Although the audible alarm silences, the condition that caused the alarm to sound may still
exist.
If a utility power failure caused the alarm, the alarm silences after power is restored.
For information about audible alarm conditions, see "LED and audible alarm troubleshooting (on page 94)."
Abnormal output voltage at startup
Possible cause: The system is not configured as parallel.
Action:
1. Verify the Parallel UPS Card wiring connections. See "Configuring the Parallel UPS Card (on page
41)."
2. Be sure that the line cord is installed properly.
3. Power down the UPS where the alarm is indicated.
o Standalone UPS configurationSee "Powering down the standalone UPS (on page 72)."
o Individual UPS in a parallel configurationSee "Powering down an individual paralleled UPS (on
page 72)."
o Parallel UPS configurationSee "Powering down the parallel system (on page 73)."
4. Power up the UPS.
o Standalone UPS configurationSee "Powering up the standalone UPS (on page 25)."
o Parallel UPS configurationSee "Powering up the parallel system (on page 39)."
5. Select the TURN SYSTEM ON option through the front panel of the UPS that was powered down.
Battery breaker
Possible cause: The UPS does not recognize the internal batteries.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R1500 - UPS XR and is the answer not in the manual?

HP R1500 - UPS XR Specifications

General IconGeneral
TopologyLine Interactive
Input ConnectionIEC 320 C14
Battery TypeSealed Lead Acid (SLA)
Form FactorRackmount
Nominal Output Voltage230V
Nominal Input Voltage230V
Input Frequency50/60 Hz
Typical Backup Time at Full Load5 minutes
Transfer Time4-8 ms
Hold-up Time10 ms
Input Voltage Range160 - 286 VAC
Interface PortUSB
Battery Recharge Time3 hours
Communication PortsUSB
WaveformSine wave