Communication 79
Metering
The Output and Load Receptacle meter readings differ between a parallel system and a standalone UPS. In
a parallel system, one UPS reads the Load Receptacle value for the total system (the others read zero), but
each UPS displays its own Output value. For example, in a two-unit parallel system with one Anderson load
connection for 12 kVA, the Load Receptacle current would read 12 kVA on one UPS and zero on the other
UPS, but the Output measurement would be 6 kVA on each UPS (half the total). In a standalone UPS, the load
can be connected from the outlet cord or the Anderson load connector. The Output measurement would be
the total load on the UPS, and the Load reading would be the portion supplied by the Anderson load
connector.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R1500 - UPS XR and is the answer not in the manual?

HP R1500 - UPS XR Specifications

General IconGeneral
TopologyLine Interactive
Input ConnectionIEC 320 C14
Battery TypeSealed Lead Acid (SLA)
Form FactorRackmount
Nominal Output Voltage230V
Nominal Input Voltage230V
Input Frequency50/60 Hz
Typical Backup Time at Full Load5 minutes
Transfer Time4-8 ms
Hold-up Time10 ms
Input Voltage Range160 - 286 VAC
Interface PortUSB
Battery Recharge Time3 hours
Communication PortsUSB
WaveformSine wave

Related product manuals