Maintenance 88
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of
the UPS regularly with a vacuum cleaner.
Maintain the ambient temperature at 25°C (77°F).
If storing a UPS for an extended period, recharge the batteries every 6 months:
CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep these
batteries charged while in storage is implemented.
a. Connect the UPS to utility power.
b. Allow the UPS to remain in Standby mode.
c. Allow the UPS to charge the batteries for at least 24 hours.
d. Update the battery recharge date label.
UPS battery replacement procedure
This component is hot-swappable and can be replaced without powering down the UPS.
1. (optional) To replace the component with the UPS powered down, do one of the following:
o Standalone UPS configurationSee "Powering down the standalone UPS (on page 72)."
o Individual UPS in a parallel configurationSee "Powering down an individual paralleled UPS (on
page 72)."
o Parallel UPS configurationSee "Powering down the parallel system (on page 73)."
CAUTION: When hot-swapping batteries, the load is not protected in the event of a utility power
failure, unless at least one ERM is installed.
2. Remove the UPS front bezel ("Removing the UPS front bezel" on page 81).
NOTE: Disconnecting the control panel from the electronics module automatically transfers the
UPS to Auto-Bypass mode. However, HP recommends transferring the UPS to Auto-Bypass mode
manually BEFORE disconnecting the control panel to provide extra protection to the electronics
module.
3. Remove the UPS battery bracket ("Removing the UPS battery bracket" on page 19).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R1500 - UPS XR and is the answer not in the manual?

HP R1500 - UPS XR Specifications

General IconGeneral
TopologyLine Interactive
Input ConnectionIEC 320 C14
Battery TypeSealed Lead Acid (SLA)
Form FactorRackmount
Nominal Output Voltage230V
Nominal Input Voltage230V
Input Frequency50/60 Hz
Typical Backup Time at Full Load5 minutes
Transfer Time4-8 ms
Hold-up Time10 ms
Input Voltage Range160 - 286 VAC
Interface PortUSB
Battery Recharge Time3 hours
Communication PortsUSB
WaveformSine wave