Event
code
Message text and description Details and solution
2060 Chassis CPU maximum temperature
exceeded. Shutting down the system.
• Verify that the ambient air temperature is
within acceptable limits.
• Verify that nothing is obstructing airflow from
the front or back of the library.
2061 Move failed pulling cartridge from drive. Check for labels or cartridge misalignments that
would prevent the cartridge from coming out of
the drive.
2062 Move failed inserting cartridge into drive. Check for labels or cartridge misalignments that
would prevent the cartridge from being inserted
into the drive.
2063 Move failed positioning picker in front of
drive.
• Check for additional events that might
provide an indication of the reason for the
failure.
• Check for obstructions in the vertical or
horizontal pathway of the robotics assembly,
such as a cartridge that is not seated
completely in a slot or a problem with the
robotic spooling cable that is impeding
progress.
• Verify that the robotic assembly is level
within the module. If the module was
recently moved or the robotic assembly
replaced, the assembly could be out of
alignment.
2064 Library test failed with critical error.
1. Check for additional events that might
provide an indication of the reason for the
failure.
2. Verify that the minimum requirements are
met for the test and then retry the test.
3. To verify robotic movement, perform a slot-
to-slot or element-to-element test.
2065 Library startup process failed because of
robotics initialization issue.
• Check for obstructions, such as a cartridge
sticking out, in the vertical pathway of the
robotics assembly.
• Check for objects in the bottom of the library
blocking the path of the robotic assembly.
Table Continued
208 Event codes