Event code Message
9045 Library configuration data failed to duplicate onto the base module.
1. Attempt to save the library configuration from the Configuration > System, Save/
Restore Configuration screen. If additional information, see Saving the library
configuration on page 57.
2. Power cycle the library.
3. Retry the operation.
9046 The chassis fan speed could not be determined. This is not a critical event. This fan
provides enhanced cooling for unusually high temperature environments. The chassis fan
can be removed without interrupting the library operation. Remove the chassis fan, check
for any obstructions in the fan, and reinsert it. If the chassis fan event persists after it is
removed and reinserted, the fan should be replaced when convenient.
9047 MSL Encryption Kit backup has been initiated
9048 MSL Encryption Kit restore has been initiated.
9049 MSL Encryption Kit partial backup has been initiated.
9050 More than five invalid MSL Encryption Kit PIN attempts.
9051 MSL Encryption Kit key server token contains keys that have not been backed up.
9052 MSL Encryption Kit key server token is full. Adding or generation new keys is prohibited.
9053 MSL Encryption Kit key provided.
9054 Not at BOT without read.
9055 MSL Encryption Kit key server token not present.
9056 MSL Encryption Kit key server token was inserted.
9057 MSL Encryption Kit key server token was removed.
9058 Power supply fan failed.
Event codes 237