EasyManua.ls Logo

HPE ProLiant DL345 Gen11 - Results; Removing and replacing a fan; About this task; Procedure

HPE ProLiant DL345 Gen11
341 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ResultsResults
To replace the component, reverse the removal procedure.
Removing and replacing a fanRemoving and replacing a fan
About this taskAbout this task
CAUTION:CAUTION: To maintain proper system cooling, do not operate the server for long period with the access panel open or
removed. Operating the server in this manner results in an improper system airflow. For internal hot-plug component
procedures, complete the procedure within 60 seconds. Failure to do so can cause the system temperature to increase and
trip the safety threshold. When this happens:
The health LED flashes amber.
The operating system gracefully shuts down.
CAUTION:CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless all bays are populated with
either a component or a blank.
IMPORTANT:IMPORTANT:
The fan setup can either be standard, single-rotor fans or high-performance, dual-rotor fans. Do not mix fan types in the
same server.
ProcedureProcedure
1. If installed, open the cable management arm.
HPE ProLiant DL345 Gen11 Server Service and Maintenance Guide 86

Table of Contents

Related product manuals