Shenzhen Hpmont Technology Co., Ltd. Appendix A Parameters
HD3N Series User Manual V1.1 - 121 -
Ref. Code
Function
Setting Range Default
Unit
Attribute Setting
F06.12
Multi-frequency
command 13
F00.09 - upper limit frequency 5.00Hz 0.01Hz
F06.13
Multi-frequency
command 14
F00.09 - upper limit frequency 5.00Hz 0.01Hz
F06.14
Multi-frequency
command 15
F00.09 - upper limit frequency 5.00Hz 0.01Hz
F06.15
Simple PLC control
selection
0: PLC is invalid
1: PLC is enabled
0 1
×
F06.16
Simple PLC running mode
selection
Unit: PLC running selection
0: Stop after single loop
1: Runs at final value after single loop
2: Continous loop
Ten: restart mode after stop during
PLC
0: Start from the first frequency
1: Start from the frequency when
HD3N stops
2: Runs at the moment when signal
loss
Hundred: PLC state saving selection
at power failure
0: Do not save
1: Save
Thousand: PLC phase time unit
0: Second (s)
1: Minute (m)
0000 1
×
F06.17 PLC phase 1 setting
Unit: PLC phase frequency selection
0: Multi frequency commmand
1: Set by F00.1
Ten: PLC phase direction selection
0: Forward
1: Reverse
2: Set by running command
Hundred: PLC phase Acc. / Dec. time
selection
0: Acc. / Dec. time 1
1: Acc. / Dec. time 2
2: Acc. / Dec. time 3
3: Acc. / Dec. time 4
4: Set by Acc. / Dec. speed
420 1
F06.19 PLC phase 2 setting 420 1
F06.21 PLC phase 3 setting 420 1
F06.23 PLC phase 4 setting 420 1
F06.25 PLC phase 5 setting 420 1
F06.27 PLC phase 6 setting 420 1
F06.29 PLC phase 7 setting 420 1
F06.31 PLC phase 8 setting 420 1
F06.33 PLC phase 9 setting 420 1
F06.35 PLC phase 10 setting 420 1
F06.37 PLC phase 11 setting 420 1
F06.39 PLC phase 12 setting 420 1
F06.41 PLC phase 13 setting 420 1
F06.43 PLC phase 14 setting 420 1
F06.45 PLC phase 15 setting 420 1