NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
6 System Operation and Maintenance
Copyright © Huawei Technologies Co., Ltd.
172
Alar
m
ID
Alarm
Alarm
Severit
y
Default
Value
Impact
Possible Cause
Solution
a069
Comp
start
failed
Major
N/A
The alarm
is
generated
.
1. The comp is in lack of
oil.
2. The comp driver is
faulty.
3. The comp is faulty.
1. Fill oil to the comp.
2. Maintain or replace the
comp driver.
3. Maintain or replace the
comp.
a070
Comp
drive
fan fault
Major
N/A
The alarm
is
generated
.
The fans in the comp driver
are faulty.
Check the fans in the
comp driver.
a071
Comp
drive
module
overhea
t
Major
N/A
The alarm
is
generated
.
1. The fans in the comp
driver are faulty.
2. Dirt exists in the air
vents of the fans in the
comp driver.
1. Check the fans in the
comp driver.
2. Clean the air vents of
the fans in the comp
driver.
a072
Comp
drive U
phase
loss
Critical
N/A
The alarm
is
generated
.
1. The cables to phase U
of the comp driver are
loose or damaged.
2. The comp driver is
faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
a073
Comp
drive V
phase
loss
Critical
N/A
The alarm
is
generated
.
1. The cables to phase V
of the comp driver are
loose or damaged.
2. The comp driver is
faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
a074
Comp
drive W
phase
loss
Critical
N/A
The alarm
is
generated
.
1. The cables to phase W
of the comp driver are
loose or damaged.
2. The comp driver is
faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
a075
Comp
phase
current
alarm
Major
32 A
The alarm
is
generated
, and the
compress
or shuts
down.
1. The comp is in lack of
oil.
2. The condenser fins are
blocked.
3. The outdoor units do
not run properly.
4. The solenoid valve is
faulty.
5. The refrigerant is
overfilled.
6. The comp is faulty.
1. Fill oil to the comp.
2. Clean the condenser
fins.
3. Maintain or replace the
outdoor units.
4. Maintain or replace the
solenoid coil or the
solenoid valve.
5. Decrease certain
amount of refrigerant.
6. Maintain or replace the
comp.