NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
3 Installation Guide
Copyright © Huawei Technologies Co., Ltd.
46
Figure 3-21 Securing the cabinet
----End
3.6.2 Installing an Indoor Unit in Non-securing Mode
Prerequisites
Non-securing mode applies to scenarios where the indoor unit is to be installed on a floor
while no base is available.
Procedure
Step 1 Place the cabinet.
1. Determine the installation position according to the plan.
2. Move the cabinet to the installation position.
Step 2 Level the cabinet.
1. Raise the cabinet by adjusting the leveling feet using a wrench, as shown in Figure 3-22.
Ensure that the leveling feet contact the floor and the castors hang in the air.
Spin the castors. If the castors rotate freely, they are hanging in the air.