NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Copyright © Huawei Technologies Co., Ltd.
Conductivity rate at 20°C (σ
20
)
a
a: When σ
20
is less than 300 μS/cm, the first vapor exhausting duration of the humidifier is
long; when σ
20
greater than 1250 μS/cm, the humidifier service life is affected.
2.4 Technical Specifications
Table 2-10 General Parameters
2000 mm x 600 mm x 1100
mm
2000 mm x 600 mm x 1100
mm
a: Indoor dry-bulb temperature: 37.8°C. Wet-bulb temperature: 20.8°C. Condensing
temperature: 45°C.
b: Frames can be used to expand the depth to 1200 mm, while top supports can be used to
top frame to 2200 mm.
When the total load of servers, relative to a single smart cooling product, is less than 10
kW, smart cooling products that have heating and humidification functions or partial
heating and humidification functions are recommended.
The condensate pump is mandatory for scenarios where pipes are routed from the top or if
it is required by the customer.
Table 2-11 Optional Parameters of NetCol5000-A035
NetCol5000-A
035H512D2E1
20E1
NetCol5000-A
035H512D2E1
20E0
NetCol5000-A
035H512D200
20E1
NetCol5000-A
035H512D200
20E0