NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Copyright © Huawei Technologies Co., Ltd.
Figure 3-53 Connecting monitoring cable
3.12 Connections Verification
Table 3-18, Table 3-19, and Table 3-20 list the items for connections verification.
Table 3-18 Check items on the indoor unit
The cabinet is installed properly, without any
tilts.
The cabinet is secured to the base by using bolts.
The foreign matter inside the cabinet such as
cable ties and stubs is cleaned up.
The electric heater is secured.
The electric heater probe is secured.
The fan has no foreign matter inside.
The fan blades rotate properly.
The water inlet pipes and drainpipes are securely
connected without leakage.
The electrode humidifier is securely connected to
its base.