NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Copyright © Huawei Technologies Co., Ltd.
Figure 2-6 Networking diagram
2.3 Working Conditions
Environmental Specifications
Do not install the smart cooling product near a noise-sensitive place such as an office or a conference
room.
Table 2-4 Operation conditions
Ambient temperature of
NetCol5000-A025
Connecting with NetCol500-A032: –20°C to +45°C
(If low-temperature component is used, the lowest
temperature is –40°C.)
Connecting with NetCol500-A036: –20°C to +52°C
Connecting with NetCol500-A038: –20°C to +55°C
Ambient temperature of
NetCol5000-A035
Connecting with NetCol500-A036: –20°C to +45°C
(If low-temperature component is used, the lowest
temperature is –40°C.)
Connecting with NetCol500-A038: –20°C to +45°C
Connecting with NetCol500-A072: –20°C to +55°C
Indoor unit: IP20
Outdoor unit: IPX5
0 to 1000 m (If the altitude is greater than 1000 m, the
cooling performance deteriorates. Table 2-6 describes
the derating coefficients.)