NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
4 ACC Introduction
Copyright © Huawei Technologies Co., Ltd.
90
Parameter
Specification
Setting Method
EMS port
-
It is recommended that you retain the default value
16100. If you need to change the value, enter a value as
required. This parameter is configurable when
Connection mode is set to Client.
----End
4.3.2.6 Setting SNMP Parameters
Context
To set communications parameters, log in as the Admin, or Engineer user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a smart
cooling product to an NMS (network management system).
One smart cooling product supports concurrent access of up to 10 NMSs through SNMP.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings. Figure 4-9 is
displayed.
Figure 4-9 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then click Submit.
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read Community and
Write Community by performing Step 3.
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing Step 4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A-035 and is the answer not in the manual?

Huawei NetCol5000-A-035 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A-035
CategoryAccessories
LanguageEnglish

Related product manuals