EasyManua.ls Logo

Huawei NetCol5000-A-035 - Page 35

Huawei NetCol5000-A-035
223 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
3 Installation Guide
Copyright © Huawei Technologies Co., Ltd.
26
Figure 3-1 Checking refrigerant
Table 3-7 Mapping between temperatures and R410A saturation pressure
Temperature
C)
Saturation
Pressure-S
urface
Pressure
(MPa)
Temperature
C)
Saturation
Pressure-S
urface
Pressure
(MPa)
Temperatur
e (°C)
Saturati
on
Pressure
-Surface
Pressure
(MPa)
0
0.7
19
1.31
38
2.21
1
0.73
20
1.35
39
2.27
2
0.75
21
1.39
40
2.33
3
0.78
22
1.4
41
2.39
4
0.81
23
1.47
42
2.45
5
0.84
24
1.51
43
2.51
6
0.87
25
1.56
44
2.57
7
0.9
26
1.60
45
2.63
8
0.93
27
1.65
46
2.7
9
0.96
28
1.69
47
2.76
10
0.99
29
1.74
48
2.83
11
1.02
30
1.79
49
2.9
12
1.05
31
1.84
50
2.97
13
1.09
32
1.89
51
3.04
14
1.12
33
1.94
52
3.11
15
1.16
34
1.99
53
3.19
16
1.19
35
2.04
54
3.26
17
1.23
36
2.1
55
3.34

Table of Contents