NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
3 Installation Guide
Copyright © Huawei Technologies Co., Ltd.
33
When calculating the height difference, the compressor base is regarded as the baseline for
the indoor unit.
The inverted trap should be higher than the top copper pipe of the condenser.
In the figure, is a sign of a tilt, indicating that the scale of the pipe tilting is at least
1:200. The pipe tilting direction should be consistent with the hypotenuse of the right
triangle.
If the indoor unit is placed higher than or equal to the outdoor unit, inverted traps or oil
traps are not needed.
Figure 3-6 Routing pipes from the bottom
(1) Inverted traps
(2) Oil traps
(3) Tilted gas pipe
(4) Tilted liquid pipe
Figure 3-7 Routing pipes from the top
(1) Inverted traps
(2) Oil traps
(3) Tilted gas pipe
(4) Tilted liquid pipe