Earth Leakage Limit — In the dialog box, enter the limit, in Amps. The limit is the threshold
where Neo5 will give an Earth Leakage Alarm.
No Response Limit — This is a global setting that determines how long the system should
apply 96% power or more without a 5 degree rise in the temperature before it is declared an
alarm condition. The default value is 4 minutes and the valid range is 2 to 15 minutes.
No Heater Detected Enable — The No Heater Detected Alarm supplies instantaneous
feedback that a heater has failed or is no longer connected to the circuit. Touch the No Heater
Detected Enable box to enable the No Heater Detected feature.